ICode9

精准搜索请尝试: 精确搜索
首页 > 其他分享> 文章详细

ABB AC 900F学习笔记112:Freelance_Engineering_Process_Stations-18

2021-09-02 14:31:27  阅读:226  来源: 互联网

标签:900F ABB redundancy Stations fault 控制器 module 冗余 Secondary


继续学习

5.1.3 Redundancy criteria

冗余准则

A redundancy toggle between Primary and Secondary is forced when the self-test diagnosis reveals the following conditions:

当自建诊断显示以下情况时,强制在主(控制器)和备(控制器)之间发生冗余切换。

  • a module fault has occurred (a module fault is also detected, when a fieldbus module is switched off),
  • 模块故障发生(当现场总线模块关闭时,也检测到模块故障)
  • an equipment fault has been detected on the fieldbus module
  • 现场总线模块上检测到模块故障
  • the watchdog has responded due to a controller hardware error
  • 看门狗相应控制器硬件错误
  • a power fail of the power supply is reported
  • 报告电源故障
  • a network fault has occurred
  • 发生网络故障
  • a “fatal software error” has occurred
  • 发生致命软件错误

If the redundant link is interrupted, a redundancy toggle is initiated. The previous Primary remains in the “no operating system“ status. When the redundancy link is re-established, a reset must be initiated in the Secondary.

如果冗余链路断开,则启动冗余切换。之前的Primary仍然处于“无操作系统”状态。当冗余链路重新建立时,必须在从备(控制器)启动复位。

 

If the Ethernet interface for the redundancy link on the Secondary fails, no redundancy toggle is performed. When the Ethernet interface for the redundancy link on the Secondary operates again, a reset must be initiated in the Secondary. 

如果冗余链路的以太网接口故障,冗余切换不会执行。当备控制器上的冗余链路以太网接口再次运行时,必须从备控制器复位操作。

 

标签:900F,ABB,redundancy,Stations,fault,控制器,module,冗余,Secondary
来源: https://www.cnblogs.com/fishingsriver/p/15218556.html

本站声明: 1. iCode9 技术分享网(下文简称本站)提供的所有内容,仅供技术学习、探讨和分享;
2. 关于本站的所有留言、评论、转载及引用,纯属内容发起人的个人观点,与本站观点和立场无关;
3. 关于本站的所有言论和文字,纯属内容发起人的个人观点,与本站观点和立场无关;
4. 本站文章均是网友提供,不完全保证技术分享内容的完整性、准确性、时效性、风险性和版权归属;如您发现该文章侵犯了您的权益,可联系我们第一时间进行删除;
5. 本站为非盈利性的个人网站,所有内容不会用来进行牟利,也不会利用任何形式的广告来间接获益,纯粹是为了广大技术爱好者提供技术内容和技术思想的分享性交流网站。

专注分享技术,共同学习,共同进步。侵权联系[81616952@qq.com]

Copyright (C)ICode9.com, All Rights Reserved.

ICode9版权所有